← Portal

Load Calculator

Enter the electrical load and the system automatically calculates conductor, breaker, conduit, and ground — all per NEC 2023.

Or enter watts below
Auto-calculates amps from watts ÷ voltage
1Type
2System
3Loads
4Conductors
5Panel
6Results
🏗️

Step 1 — Installation Type

Select the type of installation to begin the NEC compliance wizard.

🏠
Residential
NEC Article 210, 220, 230
🏢
Commercial
NEC Article 210, 215, 220
🏭
Industrial
NEC Article 430, 440, 450
Service Entrance
NEC Article 230
⚙️
Motor Circuit
NEC Article 430
☀️
Solar / PV System
NEC Article 690
🔍

Conductor Ampacity — NEC Table 310.16

NEC 310.16 · 0–2000V, 60–75–90°C
AWG/kcmilCu 60°CCu 75°CCu 90°CAl 60°CAl 75°CAl 90°C
#1415A20A25A
#1220A25A30A15A20A25A
#1030A35A40A25A30A35A
#840A50A55A30A40A45A
#655A65A75A40A50A60A
#470A85A95A55A65A75A
#385A100A110A65A75A85A
#295A115A130A75A90A100A
#1110A130A150A85A100A115A
#1/0125A150A170A100A120A135A
#2/0145A175A195A115A135A150A
#3/0165A200A225A130A155A175A
#4/0195A230A260A150A180A205A
250 kcmil215A255A290A170A205A230A
300 kcmil240A285A320A195A230A260A
350 kcmil260A310A350A210A250A280A
400 kcmil280A335A380A225A270A305A
500 kcmil320A380A430A260A310A350A
600 kcmil355A420A475A285A340A385A
⚠ When using 75°C rated terminals (most equipment), use the 75°C column even if conductor is rated 90°C. Always derate for ambient temperature and conduit fill per NEC 310.15(B).

Conduit Fill — NEC Chapter 9, Table 1

NEC Ch.9 Table 1 · EMT · RMC · PVC 40 · PVC 80
Trade Size1 conductor (53%)2 conductors (31%)3+ conductors (40%)EMT Area (in²)
½"0.16 in²0.09 in²0.12 in²0.304
¾"0.26 in²0.15 in²0.20 in²0.533
1"0.43 in²0.25 in²0.35 in²0.864
1¼"0.76 in²0.44 in²0.60 in²1.496
1½"1.06 in²0.61 in²0.83 in²2.036
2"1.74 in²1.01 in²1.34 in²3.356
2½"3.08 in²1.79 in²2.31 in²5.858
3"4.61 in²2.68 in²3.46 in²8.846
3½"6.08 in²3.53 in²4.57 in²11.545
4"7.83 in²4.55 in²5.90 in²14.753
Conductor area reference: #14=0.0097, #12=0.0133, #10=0.0211, #8=0.0471, #6=0.0590, #4=0.0814, #2=0.1333, #1=0.1562, 1/0=0.1963, 2/0=0.2463, 3/0=0.3107, 4/0=0.3904 in²

Standard OCPD Ratings — NEC 240.6

NEC 240.6(A) · Standard ampere ratings
{['15','20','25','30','35','40','45','50','60','70','80','90','100','110','125','150','175','200','225','250','300','350','400','450','500','600','700','800','1000','1200','1600','2000','2500','3000','4000','5000','6000'].map(a=>`${a}A`).join('')}
Real-world field sizes (commonly stocked): 15, 20, 30, 40, 50, 60, 70, 100, 125, 150, 200, 225, 400, 600A. Sizes 25A, 35A, 45A, 90A, 110A exist per NEC 240.6(A) but are specialty/hard to find. 80% Rule (NEC 210.20): Continuous loads must not exceed 80% of breaker rating — size breaker at 125% of load. NEC 240.4(D): #14 Cu max 15A, #12 Cu max 20A, #10 Cu max 30A — regardless of load.

Equipment Grounding Conductor — NEC Table 250.122

NEC 250.122 · Based on OCPD rating
OCPD Rating (A)Cu EGCAl EGC
15#14 AWG#12 AWG
20#12 AWG#10 AWG
30–60#10 AWG#8 AWG
100#8 AWG#6 AWG
200#6 AWG#4 AWG
300–400#4 AWG#2 AWG
500–600#2 AWG#1/0 AWG
800#1/0 AWG#3/0 AWG
1000–1200#2/0 AWG#4/0 AWG
1600–2000#3/0 AWG250 kcmil

Demand Factors — NEC Article 220

NEC 220.42, 220.50, 220.54, 220.55
Load TypeDemand FactorNEC Ref
Lighting — first 3,000 VA100%220.42
Lighting — 3,001 to 120,000 VA35%220.42
Lighting — over 120,000 VA25%220.42
Small appliance circuits (residential)100%220.52
Electric dryer — first 4100%220.54
Electric dryer — 5–23 units85–35%220.54
Largest A/C or heating unit100%220.60
Remaining A/C or heatingUse larger of the two loads220.60
Motor loads125% of largest + 100% others430.24
NEC 220.60: Only the larger of the A/C or heating load needs to be calculated — not both simultaneously (they don't run at the same time).

Ambient Temperature Correction — NEC 310.15(B)(1)

NEC 310.15(B)(1) · Multiply ampacity by correction factor
Ambient °CAmbient °F60°C factor75°C factor90°C factor
21–25°C70–77°F1.081.051.04
26–30°C78–86°F1.001.001.00
31–35°C87–95°F0.910.940.96
36–40°C96–104°F0.820.880.91
41–45°C105–113°F0.710.820.87
46–50°C114–122°F0.580.750.82
51–55°C123–131°F0.410.670.76
56–60°C132–140°F0.580.71
⚠ Puerto Rico: Outdoor ambient typically 35–40°C. Attics and direct sun exposure can reach 45–50°C. Always apply correction factor for PR installations.

Motor Circuit Requirements — NEC Article 430

NEC 430.22, 430.52, 430.32 · Branch circuit sizing
ComponentMultiplierNEC RefNotes
Branch circuit conductorFLA × 125%430.22Minimum ampacity
Overload protectionFLA × 115–125%430.32115% SF≥1.15, 125% others
Inverse time breakerFLA × 250%430.52(C)Maximum OCPD
Instantaneous trip breakerFLA × 800–1300%430.52(C)Motor controller required
Dual-element fuseFLA × 175%430.52(C)Time-delay type
Multiple motors feederLargest × 125% + others × 100%430.24Feeder sizing
Service Factor (SF): If the motor nameplate shows SF ≥ 1.15, overload protection can be set at 125% FLA. Otherwise 115% maximum.

AFCI & GFCI Requirements — NEC 210.8 / 210.12

NEC 210.8(A)(B) · 210.12(A)(B) · 2023 edition
LocationGFCI RequiredAFCI Required
Bathroom✅ Yes — 210.8(A)(1)✅ Yes — 210.12
Kitchen (countertop)✅ Yes — 210.8(A)(6)✅ Yes — 210.12
Garage✅ Yes — 210.8(A)(2)✅ Yes — 210.12
Outdoors✅ Yes — 210.8(A)(3)❌ No
Basement (unfinished)✅ Yes — 210.8(A)(5)✅ Yes — 210.12
Crawl space✅ Yes — 210.8(A)(4)❌ No
Bedroom❌ No (unless within 6ft of sink)✅ Yes — 210.12
Living areas❌ No✅ Yes — 210.12
Pool / spa✅ Yes — 680❌ No
Commercial kitchens✅ Yes — 210.8(B)Varies

Conductor Color Code — NEC 200.6 / 210.5

NEC 200.6, 210.5(C) · Color identification
ConductorRequired ColorSystem
Grounded (Neutral)White or GrayAll systems
Equipment Ground (EGC)Green, Green/Yellow, BareAll systems
Ungrounded (Hot) Phase ABlackAll systems
Ungrounded (Hot) Phase BRed120/240V or 208V 3Ø
Ungrounded (Hot) Phase CBlue208V / 480V 3Ø
Hot — 277V (from 480V)Brown480V Wye
Hot Phase B — 480VOrange480V Wye
Hot Phase C — 480VYellow480V Wye
High-leg Delta (208V)Orange240V Delta
NEC does not mandate color for ungrounded conductors #6 AWG and larger — field marking with tape is acceptable. White re-identified with tape = ungrounded conductor ≥ #4 AWG (200.7(C)).

Box Fill Calculation — NEC 314.16

NEC 314.16(B) · Conductor volume allowances
Wire SizeVolume per conductor (in³)
#18 AWG1.50 in³
#16 AWG1.75 in³
#14 AWG2.00 in³
#12 AWG2.25 in³
#10 AWG2.50 in³
#8 AWG3.00 in³
#6 AWG5.00 in³
Count: Each hot + neutral = 1 each. All grounds combined = 1. Device (receptacle/switch) = 2 conductors of largest wire. Cable clamps combined = 1. Internal cable clamps = 0 if cable connector is outside.
📋

NEC Compliance Report

📋
Run the Load Calculator or Installation Wizard to generate a compliance report